get a quote
Inquiry
Form loading...
Products Categories
Featured Products

Huazheng VLF Test Equipment Cable Test Multifunction Vlf Hipot And Tan Delta Tester

The VLF Multifunction Hipot Tester is an advanced electrical testing instrument designed to ensure the safety and reliability of high-voltage electrical equipment. VLF stands for Very Low Frequency, a testing method that uses low-frequency AC voltage, typically around 0.1 Hz, to perform dielectric withstand tests on cables and other electrical components. This technology has become increasingly important in the electrical industry due to its ability to accurately assess insulation integrity without causing damage.

    Introduction​​

    1.1 Product Features Introduction

    This product utilizes digital frequency conversion technology and is controlled by a microcontroller, fully automating voltage boost, buck, measurement, and protection. Due to its fully electronic nature, it is small in size and light in weight. It features a large, color touchscreen display that is clear, intuitive, and easy to operate, displaying the output waveform. Key features are as follows:

    1.1.1 Ultra-low frequency circuits with a rated voltage of 60kV or less adopt an integrated structure; ultra-low frequency circuits with a rated voltage greater than 60kV adopt an integrated unit connected in series with a step-up transformer, which greatly reduces the overall weight, enhances the load-carrying capacity, and achieves multiple uses in one unit. Operation is extremely simple.

    1.1.2 Current and voltage data are directly sampled from the high-voltage side. Due to the use of a closed-loop negative feedback control circuit, there is no capacitive rise effect in the output.

    1.1.3 Intelligent Integrated Protection Function: Without needing to set current and voltage protection values, the instrument can calculate overvoltage and overcurrent protection values based on the sample capacitance and test voltage. It can trigger protection shutdown for overvoltage, overcurrent, low resistance faults in the sample, and flashover .

    1.1.4 It adopts a 150kV high-voltage line output, which is safe and reliable.

    Version 1.1.5 adds DC, dielectric loss, and partial discharge testing functions, allowing simultaneous measurement of the sample's dielectric loss, capacitance, insulation resistance, and partial discharge during withstand voltage testing. ( Dielectric loss and partial discharge functions are optional .)

    1.2 Specifications of Ultra-Low Frequency High Voltage Power Supply Series: Table 1

    Rated voltage

    Load capacity

    Exterior drawing

    Product structure, weight, and application scope

    30kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity: ≤10 µF


    All-in-one machine weight (30kV): 30kg

    Used for withstand voltage testing of cables and motors up to 10KV.

    40kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity: ≤10 µF

     

    All-in-one machine weight (40kV): 30kg

    Used for withstand voltage testing of cables and motors up to 10KV.

    50kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity: ≤6 µF

     

    All-in-one machine weight (50kv): 35kg

    Used for withstand voltage testing of cables and motors up to 20KV.

    60kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity: ≤5 µF


    All-in-one machine weight (60kv): 35kg

    Used for withstand voltage testing of cables and motors up to 25KV.

    80kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity:

    ≤10 µF (within 40k),

    ≤4 µF (above 40kV)


    All-in-one machine weight (40kV): 30kg

    Two-stage step-up transformer (40kV): 40kg

    Used for withstand voltage testing of cables and motors up to 35KV.

    90kV(Peak)

    Automatic frequency adjustment: 0.1Hz-0.01Hz

    Load capacity:

    ≤10 µF (within 40k),

    ≤4 µF (above 40kV)


    All-in-one machine weight (40kV): 30kg

    Two-stage step-up transformer (50kV): 40kg

    Used for withstand voltage testing of cables and motors up to 35KV.

    1.3 General Technical Specifications of Ultra-Low Frequency High Voltage Power Supply

    1.3.1 Rated output voltage: 30kV-80kV. See Table 1 for specifications.

    1.3.2 Output Frequency: Automatic frequency conversion range : 0.1Hz - 0.01Hz

    1.3.3 Load capacity: See Table 1

    1.2.4 AC voltage resolution: 0.1kV

    1.3.5 Voltage accuracy: 3 %

    1.3.6 AC current resolution: 0.1mA

    1.3.7 AC current accuracy: 3%

    1.3.8 Voltage positive and negative peak error: ≤3%

    1.3.9 Voltage waveform distortion: ≤3%

    1.3.10 Operating conditions: Indoor and outdoor; Temperature: -10 ℃ to +40 ℃; Humidity: ≤ 85 % RH

    1.3.11 Input power: 50Hz frequency , 230V ± 5% voltage ( or 60Hz frequency , 120V ± 5% voltage ) . 1.3.12 It has a grounding detection function; voltage boosting will be disabled if grounding is not enabled .