Huazheng Phasing tool HV detector Wireless Digital Non Contact High Voltage Phasing Tester

HZ-8600 Phasing Unit, for MV overhead distribution circuits, is used to detect whether the phase sequence on both sides of the high-voltage power grid closing point is the same. The phase sequence of the two power line connections must be checked beforehand; otherwise, the lines may short circuit. The instrument is suitable for 0.22 to 220 kV power transmission lines and can test whether the line is charged. The instrument adopts wireless transmission technology, ensuring safe and reliable operation and ease of use.

           Withstand Voltage Test Bench (1)

    Product Features

    Working Principle

    The instrument consists of two transmitters (X and Y) and a receiver. The two transmitters can determine whether the line is charged and launch a phase signal. The receiving meter collects signals from both transmitters to determine whether the phase sequences on both sides are the same.

    Security Matters

    1.The insulating rod should undergo a voltage withstand test before use.
    2.The standard length of the insulating rod is 3 m, suitable for voltages up to 220 kV. If the circuit voltage exceeds 220 kV, please use an insulating rod longer than 3 meters.
    3.The operator's hand position should not exceed the handle position of the insulating rod.

    Technical Characteristics

    1.Accuracy: When the phase sequence is the same, the error is ≤ 5°.
    2.Frequency accuracy: ±0.1 Hz.
    3.Measuring voltage range: 0.22 to 220 kV.
    4.The transmission distance between the transmitter and the receiving host is more than 130 meters; the maximum distance between the two transmitters is about 260 meters.
    5.Results (in phase, out of phase) are based on a standard: a phase difference of ≥ 30° indicates out of phase, while a phase difference of < 30° indicates in phase.
    6.Voice prompts include a male voice saying "in phase" and a female voice saying "phase out."
    7.The screen simultaneously displays the phase difference, frequency, waveform, and vector diagram for the two lines.
    8.The host indicates battery status and has an automatic shutdown feature after half an hour of inactivity.
    9.Both the two transmitters and the receiver use rechargeable lithium batteries.
    10.A high-pressure test report is available, confirming the function of the phase sequence.
    11.During high-pressure measurements, the leakage current is < 10 µA.
    12.Transmitter power consumption is < 0.1 W; the receiving host's power consumption is < 0.3 W.
    13.The host's lithium battery capacity is approximately 2200 mAh, while the transmitter battery capacity is about 350 mAh.
    14.Working environment: temperature -35 °C to +45 °C; humidity ≤ 95% RH.
    15.Storage conditions: temperature -40 °C to +55 °C; humidity ≤ 95% RH.
    16.Weight: approximately 5 kg.
    17.Instrument package dimensions: 71 cm long, 26 cm wide, and 11 cm high.
    The voltage level instructions:
    The voltage level instructions Instructions Added
    500KV Launcher insulating rod (5 meters), the hook on the high tension line directly, host boot.  Conventional
    330KV Launcher insulating rod (4 meters), the hook on the high tension line directly, host boot. Conventional
    220KV Launcher insulating rod (3 m), direct hook on the high tension line, the host boot. Conventional
    110KV Auncher insulating rod (3 m), direct hook on the high tension line, the host boot Conventional
    35KV Launcher insulating rod (3 m), direct hook on the high tension line, the host boot. Conventional
    10KV(bare wire) Launcher insulating rod (3 m), direct hook on the high tension line, the host boot. Conventional
    380V/220V Use the special test line of mains connection launcher (as shown in figure 1), the host boot. Use the special test line of mains
    Switchgear induction electric (~ 5 V) Use switchgear induction electric test line connection transmitter (see switchgear induction electric measuring point) host boot Use switchgear induction electric test line.

    The Test Results Analysis

    Phase difference value (f) The phase difference is stable Results the judgment Added
    0~5 Stable In phase
    Two lines with the frequency,
    Such as voltage.
    115~125
    or235~245
    stable phase-out
    Two lines with the frequency,
    Such as voltage.
    0~360 Is not stable, 0 ~ 360 degrees cycle changes Two line frequency is not the same Not parallel.
    The value near 0、120、240 Stable Two line voltage is not the same.
    Two lines the same frequency, voltage,
    Not parallel.

    Instruments To Check


    Check the project Check the method Normal phenomenon Abnormal phenomenon Exception handling
    Insulating rod pressure Check pressure performance reference appendix A Leakage current is less than 10 uA Leakage current is greater than 10 uA Replace the insulation rod
    Transmitter power Unscrew the cap, dial up the transmitter switch to open position. Buzzer rang 2 seconds, the indicator light flashing in 1 and 2. The buzzer rang, or example, said the battery is low.
    The transmitter switch, connect a charger.
    After full charge indicator for the green light.
    The emitter function Use the special test line of mains connection (see figure 1), the mains. The receiving host boot. Buzzer rang 2 seconds, the indicator light flashing in 1 and 2. The receiving host display corresponding to the frequency of the transmitter. In power under normal conditions, the light is not flashing, host according to the corresponding frequency of 0 . Transmitter failure, returned to the factory maintenance.
    The host battery The host boot  The battery capacity is greater than 1 Shows the battery is too low, the host automatically power off. After connect charger, full of for the green light .
    The host wireless communications Host machine, emitter accept electric work normally. The host shows the frequency of the corresponding normal information. Host shows the frequency of the corresponding to zero. Return to factory maintenance. 

    Maintenance

    1.When not in use for an extended period, please fully charge the instrument before storage.

    2.This product should not be stored in damp, high-temperature, or dusty environments.

    3.The insulating rod should undergo a voltage withstand test before each use and annually thereafter.

    After-sales Service

    1.If quality problems arise within one month of purchase, the company will provide a free replacement.

    2.For quality issues within one year, the company offers free repairs.

    3.For instruments used for over a year, the company is responsible for long-term maintenance, with appropriate charges for materials.

    4.If the instrument malfunctions, it should be returned to the company for repair. Users are not permitted to disassemble the instrument, as any resulting damage will not be the company's responsibility.