Huazheng Manufacture HZSF-702 High Precision Portable Dew Point Tester
I.Technical Characteristics And Parameters
|
Features |
||
|
Smart calibration |
The sensor probe can automatically calibrate the zero point to ensure the readiness for each measurement; |
|
|
Quick and gas-saving |
After turning on the machine and entering the measurement state, the dew point measurement time for each SF6 air barrier is about 5 minutes; |
|
|
Safe and reliable |
It adopts self-locking joints imported from Germany, which are safe, reliable and airtight; |
|
|
Mass storage |
Adopting a large-capacity data storage design, it can store up to 250 sets of test data; |
|
|
High definition display |
Color screen directly display dew point, moisture, temperature, humidity, time, date and dew point curve; |
|
|
Moving measurement |
Built-in large capacity rechargeable lithium battery, a full charge can work for 10 hours; |
|
|
Accurate measurement |
The temperature compensation function is added to ensure the accuracy of the measurement results under various temperature conditions. |
|
|
Local calibration |
This machine comes with calibration function, do not need to connect the computer to complete the data calibration. |
|
|
Technical parameter |
||
|
dew-point |
Measuring range |
-60℃~+ 20℃ |
|
|
measurement accuracy |
±1℃ |
|
ambient temperature |
-40℃~+80℃ |
|
|
environment humidity |
0~100% RH |
|
|
Display device |
4.3-inch color touch screen |
|
|
power supply |
AC 220V;Built-in rechargeable battery: can be used for more than 10 hours on a single charge |
|
|
weight |
4.5Kg |
|
|
size |
300 mm×150 mm×300mm |
|
|
Operating temperature |
-30℃~+60℃ |
|
Instrument Panel Description
1、front panel

Note: Press the bracket adjustment buttons on both sides at the same time to adjust the angle of the bracket.
2、rear panel

Note: This model can be equipped with a printer.

Measurement Methods
Precautions
1.Placement
Place the instrument in a safe location to prevent it from falling and severe vibrations.
2.Gas Measurement
Do not measure corrosive or flammable gases.
3.Charging
Charge the instrument in a timely manner before use.
4.Charging Procedure
To charge the instrument, simply connect the power cord to a 220V socket. There is no need to turn on the power switch; the instrument will charge automatically. The charging time typically takes more than 10 hours.
5.Flow Adjustment
Before measuring, open the valve on the flow meter first, and then adjust the flow through the valve on the pipeline. Failure to do so may cause the gas in the internal pipeline of the instrument to generate pressure. Measuring under pressure can result in significantly higher readings.
Appendix:(Requirements for measuring moisture content of SF6 circuit breakers)
|
Test content |
standard (μl/l, 20℃) |
|
When the SF6 circuit breaker leaves the factory and is overhauled (before the overall installation), the moisture values of the breaking unit and the pillar unit should be measured separately. |
≤150 |
|
During handover, the moisture value of the circuit breaker is measured through the inflatable interface at the bottom of the pillar. |
≤150 |
|
During operation, the moisture value of the circuit breaker is measured through the inflatable interface at the bottom of the pillar. The test cycle is specified in the "pre-test procedures". |
≤200 |
|
During operation, if necessary (the breaking unit leaks, the breaking unit is disassembled), the water content of the breaking gas chamber of the SF6 circuit breaker should be measured separately from the self-sealing joint in the header. |
≤300 |