Huazheng Manufacture HZSF-15-50 SF6 Gas Recovery Device

This SF6 gas recovery device features an oil compressor imported from Italy. The compressor is specifically designed for SF6 gas recovery, with a displacement capacity of 6.5 m³/h and a maximum output pressure of 4.5 MPa (though the device pressure is controlled at 3.8 MPa). As a high-pressure compressor, it offers low power consumption, which significantly reduces the volume and weight of the SF6 recovery device.

           Transformer On-load Tap-changer Tester  (6)

    No.

    Indicator Name and Unit

    HZSF-15-50 

    1

    Power Supply AC

    V

    380

    2

    Rated maximum gas storage pressure(20℃)

    MPa

    ≥4

    3

    Final vacuum

    Pa

    ≤10

    4

    Vacuum maintenance of device

    Pa

    At 133 Pa pressure for 24 hours, the vacuum value increased <400 Pa

    5

    Compressor pumping rate

    m3/h

    Shenyang Valley Wheel 10m3/h Compressor

    6

    Vacuum pump pumping rate

    m3/h

    Shanghai bipolar pump 40 m3/h=15L/S

    7

    Adaptation inlet pressure of the recovery unit(20℃)

    MPa

    0~0.8

    8

    Recovery final pressure of electrical equipment(20℃)

    MPa

    ≤50 Kpa

    9

    Gas oil content control after recovery

    μg/g

    Domestic oil<10

    10

    Annual leakage rate of the device

    %

    <1

    11

    Continuous trouble-free running time of the device

    h

    ≥1000

    12

    Accumulated trouble-free running time

    h

    ≥5000

    13

    Noise level

    dB(A)

    The whole machine≤75

    14

    Actual liquid storage capacity

    KG

    50

    15

    Refrigerated liquefaction compressor

     

    Domestic Compressor

    16

    Frozen storage tank

    L

    50

    17

    Gas moisture after recovery(PPM/V)

    PPM/V

    60

    18

    Gas oil after recovery(PPM/V)

    PPM/V

    60

    19

    Dry filtration mode

     

    Vacuum heating activation regeneration

    20

    Initial inflation pressure(pa)

    pa

    ≤133

    21

    Inflation final pressure(mpa)

    mpa

    0.8

    22

    Aeration rate(m³/h)

    m³/h

    ≥5

    23

    Gasification way

     

    Automatic temperature control of electric heating

    24

    Overall dimensions

    Length * width * height

    1360×800×1300

    25

    Vacuum gauge

     

    Shanghai YunJie

    Operating Instructions 

    Operating Instructions

    1.Power Connection and Startup
    Insert the standard power cord into a power socket that meets the requirements. Turn on the power switch, and the cooling fan of the compressor will start to run.
    Note: This operation must be performed at all times. Even after work is completed, the main power supply should remain connected for at least 1 minute to ensure sufficient heat dissipation.
    2.Adjusting Suction Pressure
    Ensure the external pipeline connections are correct. Adjust the suction pressure reducing valve of the compressor to ensure that the pressure at the suction port is below 0.5 MPa. This adjustment allows the compressor to start normally and enter the working state.
    3.Starting and Stopping the Recovery Device
    Press the green start button to activate the recovery device. To stop the device, press the red stop button.
    4.Overpressure Protection
    If the outlet pressure exceeds 3.8 MPa before shutting down, the internal protection mechanism of the compressor will automatically stop the compressor to prevent damage.

    Important Instructions

    1.Particle Content in Recovered Gas

    To protect the compressor from particle pollution and wear, please install a particle filter (with a pore size less than 5 µm) on the inlet pipeline.

    2.Mixed Gas Content in Recovered Gas

    Do not use this SF6-specific compressor for any other gases. Before using the equipment, remove all gases inside using the vacuum method, reducing the pressure to 0.5 mbar.

    3.Power Supply and Wiring

    Ensure the correct use of power supply and wiring. If the compressor is used continuously for extended periods or operates under high pressure for long durations, the overheat (overcurrent) protection switch will automatically cut off the compressor’s control power. To restore operation, manual reset is required. Therefore, position the compressor so that the overheating protection switch is easily accessible for manual resetting.

    4.Safety and Maintenance

    Do not disassemble pressure equipment unless you are a professional. Avoid installing the equipment in locations where it may be struck or damaged. No modifications are allowed.

    Note: Only our professional engineers or individuals trained by us are authorized to perform maintenance and repairs.

     

     