Huazheng HZJF-9005 Portabe Handheld Multifunctional Partial Discharge Tester
I. Hardware Components
1.1 Test Host

Figure 1.1 Test Host Diagram

Figure 1.2 Test Host Operating Face
(1) MODE key, used to switch measurement modes.
(2) Power button, press the button to turn on the instrument when it is in shutdown state; in the power-on state, press and hold the power button for two seconds to turn off the instrument.
(3) Four directional keys, used for option switching, setting value modification, and chart type switching.
(4) ESC key, to exit or close a certain page. In the waveform interface, press and hold the key for two seconds to screenshot and save the current waveform.
(5) OK key, used as a confirmation key, to enter a certain page or set a certain parameter.
(6) AA/AE, contact ultrasound or non-contact ultrasound input terminal.
(7) HF, high-frequency sensor input terminal.
(8) TEV, transient voltage sensor input terminal.
(9) UHF, ultra-high frequency sensor input terminal.
(10) USB port, connects to a USB drive (FAT32 format) to save images and other files.
(11) Charger interface, input port for the charger.
(12) Headphone jack, for listening to ultrasound partial discharge with headphones.
II.Main Technical Parameters
1. Non-contact Ultrasonic Sensor (AA)
Central frequency of the sensor: 40KHz ± 1KHz
Measurement range: -7~68dBuV
Resolution: 0.1dB
Linearity error: <±20%
Sensor form: Bendable form/Focusing form
2 .Contact Ultrasonic Sensor (AE)
Detection frequency band: 20KHz~80KHz (SF6 gas-insulated power equipment)
80KHz~200KHz (Oil-filled power equipment)
Dynamic measurement range: 60dB
Resolution: 0.1dB
Linearity error: <±20%
3 .Transient Earth Voltage Sensor (TEV)
Detection frequency band: 3MHz~100MHz
Measurement range: 0~60dBmV
Resolution: 0.1dB
Linearity error: <±20%
4 .Ultra-High Frequency Sensor (UHF)
Detection frequency band: 300MHz~1500MHz
Measurement range: -70dBm to -10dBm
Effective sensor height: ≥10mm
Resolution: 0.1dBm
5. High-Frequency Sensor (HF)
Detection frequency band: 0.3MHz~30MHz
Measurement range: 0~70dB
Gain: -30~20dB
Resolution: 0.1dB
Transmission impedance: ≥10mV/mA
Input impedance: 50Ω
6 .Machine Parameters
Operating environment: Temperature -20℃~50℃, humidity 0~85%
Display screen: High-definition color 5.6-inch TFT LCD display,
resolution 480*640
Mainframe size: 230x170x48mm
Mainframe weight: 1.35Kg
Battery life: About 6 hours
III.Packing List
1. Moisture-proof
In humid climate areas or seasons, if the instrument is not used for a long time, it is advisable to turn it on and power it up once a month (about two hours) to dissipate moisture and protect the components.
2. Storage
When not in use, the instrument should be stored in an indoor environment with a temperature of -20~60℃ and a relative humidity below 85%, with ventilation and no corrosive gases.
3. Prevent exposure to direct sunlight
When using it outdoors, operate it in a shaded area as much as possible to avoid or reduce direct exposure of the display screen to sunlight.
4. Charging
The instrument uses a lithium battery as its power supply. If the battery is low, please use the included charger to charge it. Charging time is generally 2 to 4 hours. Charging is not allowed when the instrument is on, and must be done when the instrument is turned off. When charging, the charger indicator light will turn red, and it will turn green when charging is complete. Please use the charger included with the instrument.


TO KNOW MORE ABOUT Huazheng, PLEASE CONTACT US!