Huazheng HZJB-1700 Portable Handheld Three-phase Relay Protection Tester

The secondary defect elimination tester HZJB-1700 is controlled by a microcontroller, which makes it simple to use and convenient to carry. It can be used to test the action values and time of AC relays. Additionally, it can test the protection functions of low-voltage microcomputer-based line protection systems, such as re-pressurization blocking, direction overcurrent, zero-sequence overcurrent, low-cycle load reduction, and full transmission protection of high-voltage microcomputer-based line protection. The tester can also be used to check the start value, quick-break value, and second harmonic inrush blocking value for the differential protection of microcomputer-based transformers.

    6 phase relay tester (1)

    I. Test Function

    1.Manual Test: The manual test can output three AC voltages and three AC currents. The amplitude, phase, frequency, and sequence components of the AC quantities can be manually controlled with step size adjustments.
    2.State Sequence Test: This test can evaluate action times and simulate multiple failure states. Up to five states can be set. It can simulate re-closing acceleration and can also be combined with the company’s WeChat-controlled analog circuit breaker for backup self-firing tests.
    3.Low-Cycle Load Shedding Test: The unit can perform fixed-point tests for low-cycle load shedding, including action values, action times, slip lock values, voltage lock values, and current lock values.
    4.Concurrent Test: The unit can test the relevant indicators of the concurrently tested device.
    5.Harmonic Test: The unit can be used to test second harmonic inrush current blocking for transformer differential protection.
    6.Cross-Sampling Test: This unit is primarily used to measure the sampling accuracy of AC sampling devices.
    7.Remote Test: The unit can quickly open two pairs of nodes, with adjustable intermediate interval times and a minimum resolution of 1 ms.
    8.Millisecond Meter: The unit can cooperate with the system to perform open quantity and flip timing tasks.

    II.The specific functions are described as follows

    Manual test functions Can arbitrarily set the AC amount of various voltages, current amplitude, phase, and set various fault types of parameters
    Test the electrical performance of relays and protection with AC voltage (including phase voltage, line voltage, zero sequence voltage, positive sequence voltage, negative sequence voltage), AC current (including phase current, line current,) amplitude, phase, frequency, impedance and other variables.
    The step size can be manually controlled, and the step size can be changed by any setting variable
    Changes in output can be controlled
    Monitor changes in the input volume
    Action time can be tested
    Multiple continuous state tests Provides a variety of state sequence settings
    Provide a variety of time control, input control, manual trigger for state switching
    Can set various types of faults, including single grounding, two-grounding, interphase short circuit, three-phase short circuit. Fault type Instantaneous fault, permanent fault, transformational fault, and can control the fault transition time
    Can provide constant current, constant impedance and other test methods
    It can simulate the opening and closing time of the short-circuit device
    Can provide a separate voltage output as zero sequence voltage or line extraction voltage As zero sequence voltage can be set to ±3U0 or ±3√3U0; The amplitude and phase of the voltage can be set at will when the line extraction voltage is tested
    Can check the opening, opening and logical relationship of the action behavior of relays, protection and safety automatic devices
    The amplitude and phase of voltage and current can be set arbitrarily
    Can set the status parameters of various faults
    Can control each switching quantity separately

    Dedicated test function

    Low cycle load shedding
    Concurrent test
    Harmonic test
    AC sampling test
    Millisecond timing function
    Remote test

    III.Panel Introduction

    3
    HZJB-1700 Product Photo
    Keys description:
    Run/Stop: Start test/stop test
    Back delete key: When the cursor is in the current or voltage position, press the back delete key to move the cursor left or right.
      ▲▼:Move the cursor to change settings
      +-:Matching variables set increasing or decreasing values.
      Fn:Special function key, click to change the variable selection.
      Fn+1:Adjust the opening volume node 1 to carry out the action of close and disconnect.
      Fn+2:Adjust the opening volume node 2  to carry out the action of close and disconnect.
    3:Key trigger function in status sequence
      Fn+4:Initial value
      Fn+5:Short circuit calculation (This function is only available on HZJB-1700)  Fn+6:Setting key
      Fn+7:Quick constant amplitude shortcut button
      Fn+8 Fn+9:Quickly set Angle positive and negative order.
      ESC:Exit the experiment menu to the main menu.
      “.”:Enter ". "when the cursor is on the amplitude. When the cursor is in phase, the output is“-”.

    Technical Parameters

    Product Model HZJB-1700
    AC voltage output 4 channels0-130V continuously adjustable66V by default
    Output precision Accuracy0~5V Accuracy error≤±mV5V120V Accuracy error≤±0.1%±2mVResolution1mV
    Carrying capacity ≥30VA/phase
    Response time Voltage 5V~130THD%≤0.5%The voltage rise and fall time is less than 100µ s
    Phase 0-360° continuously adjustableAccuracy 0.2°Resolution 0.1°
    AC current output 3 channels0-10A
    Output precision Accuracy0.2~0.5A, Error≤2mA0.510A Accuracy error≤0.1%±2mAResolution1mA
    Current output time T330 current output time calculation formula is as follows: (Ia*Ia+Ib*Ib+Ic*Ic)*t = 600 seconds Typical current setting output time is as follows: Ia=1A, Ib =0AIc=0A output time is 600 seconds Ia=1AIb =1AIc=1A output time is 200 seconds Ia=5AIb=5AIc=5A output time is 90 seconds Ia=10A, Ib=10AIc=10A output time is 6 seconds
    Carrying capacity ≥20VA/phase
    Response time Current 0.5A~ImaxTHD% ≤0.5%The current rise and fall time is less than100µ s
    Phase 0-360° Continuously adjustableAccuracy 0.2°Resolution 0.1°
    Output frequency 0-650HzIt can simulate 11 harmonics
    Accuracy Frequency range10-65Hz Accuracy1mHz65 Hz ~250Hz Accuracy10mHz
    Opening & Closing volume Opening volume2 channels Isolation voltage is 500Vthe null contact is compatible with 32V~250V potential, and the polarity is automatically recognized Closing volumeType of 2 channels closing volume: optocoupler opening, time resolution is 0.1ms.
    Adapter DC 16.8V  5A
    Built-in battery & Endurance Built-in 20 amh lithium battery; Normal use of 8 hours
    Instrument size & Weight Less than 2.75kghand-heldsize255x210x78mm
    tester (3)
    relay protection tester  (3)