Huazheng Electric Manufacture HZYA-3Z Transformer On-load Tap-changer Tester

The Transformer On-load Tap-changer Tester is equipped with advanced technology that allows for real-time monitoring and testing of tap-changer operations without interrupting the power supply. This means you can conduct essential maintenance checks while your system remains fully operational, minimizing downtime and enhancing productivity. With its user-friendly interface, the tester simplifies complex testing procedures, making it accessible for both seasoned professionals and those new to transformer maintenance.

The on-load tap-changer is the only moving part connected to the transformer circuit. Therefore, the detection of the on-load tap-changer is becoming more and more important. In the "power equipment transfer and preventive test procedures", asked to check the on-load tap-changer action sequence, measurement switching time. The instrument is mainly used to measure the transformer on-load tap-changer transition waveform, transition time, the instantaneous transition resistance, three-phase synchronization and so on.

           Transformer On-load Tap-changer Tester  (6)

    Description

    The instrument is highly intelligent, all Chinese menu prompts, simple operation. Instrument small size, light weight, anti-interference ability, greatly reducing the labor intensity of the site staff, is the power supply units, transformer manufacturing industry to ensure safe production, improve product quality ideal instrument.

    Key features of the Transformer On-load Tap-changer Tester include high-accuracy measurement capabilities, comprehensive data logging, and intuitive software for detailed analysis. The device can assess the mechanical and electrical performance of tap-changers, identifying potential issues before they escalate into costly failures. Its robust design ensures durability in various operating environments, making it a reliable companion for field technicians and maintenance teams.

    Features

    ● Large output current, light weight;
    ● Test YO, Y, △ type transformer, the resistance unnecessary to be converted but directly display;
    ● With winding or without winding measurement;
    ● Waveform display automatically adjusts the resistance according to the sampled value, the time value amplitude
    ● With perfect protection circuit, reliability and strong;
    ● 7-inch large LCD display, easy on-site operation;
    ● Built-in high-capacity lithium battery(optional)
    ● 500 sets of data can be saved in Internal automatically, can connect with U Disk.

    Technical Parameters

    Output current: 2.0A、1.0A、0.5A、0.2A
    Measuring range Transition resistance: 0.5Ω~5Ω(2.0A)    2Ω~20Ω(1.0A)   
    5Ω~40Ω(0.5A)     20Ω~100Ω(0.2A)
    Transition time: 0 ~ 320ms
    Open circuit voltage: 24V
    Measurement accuracy Transition resistance: ± (5% reading ± 0.1Ω)
                         Transition time: ± (0.1% reading ± 0.2ms)
    Sampling rate of 20kHz
    Storage mode U disk storage
    Dimensions: 340mm × 245mm × 210mm
    Instrument weight: 7kg

    Application Conditions

    Ambient temperature   -10 ℃ ~ 50 ℃
    Ambient humidity      ≤ 85% RH 
    Power supply         AC220V±10%
    Power frequency       50 ± 1Hz
    变压器测试系列Transformer On-load Tap-changer Tester (1)Transformer On-load Tap-changer Tester  (5)Transformer On-load Tap-changer Tester (5)