Huazheng Electric HZCT-100C Current Transformer Analyzer CT PT Analyzer

With its user-friendly interface and intuitive controls, our Transformer CT PT Analyzer is easy to operate, making it suitable for both experienced professionals and those new to transformer testing. The analyzer is equipped with a range of testing capabilities, including turns ratio, winding resistance, insulation resistance, and more, providing a complete assessment of transformer performance.

    Instrument Characteristics And Parameters

    CT PT Analyzer   (8)gchCT PT Analyzer (6)i9x
    1.1Characteristics
    ★ Full-featured, not only satisfy the test requirements of various CTs (include TP class), such as the excitation characteristics (i.e., volt-ampere characteristics), ratio, polarity, secondary winding resistance, secondary burden, ratio error and phase displacement, but can also be used for the tests of various PTs, including excitation characteristics of the electromagnetic unit, ratio, polarity, secondary winding resistance, ratio error and phase displacement. 
    ★ Automatically give CT, VT parameters, including knee point voltage / current, 10% error curve, the accuracy limit factor (ALF), instrument security factor (FS), the second time constant (Ts), remanence coefficient (Kr), saturated and unsaturated inductance etc.
    ★Test meet IEC60044 GB1208 (-1) GB16847 (IEC60044-6) became etc all kinds of transformer standards, and in accordance with the transformer types and levels of automatic choose which standard test
    ★ Based on advanced principle of low-frequency test method that can meet the CT test on knee voltage up to 30KV.
    ★Friendly interface beautiful, all Chinese graphic interface
    ★ The instrument can store 2000 groups of test data that won’t be lost when power off. After test ended, the data can be coped to PC by USB disk for analysis and being transformed into WORD report.
    ★Test is simple and convenient, one-click can complete tests of CT secondary resistance, excitation, ratio and olarity.
    ★Easy to carry, because the weight is less than 9Kg.



    1.2 Panel 

    The instrument panel structure is as shown in right figure. 

    • Red S1, black S2 terminal: test power output 

    • Yellow M1, black M2 terminal: measure output voltage 

    • Green P1, black P2 terminal: measure inductive voltage

    CT PT Analyzer (2)
    1.3 Technical Parameter

    Transformer Tester

    Usage

    CT & VT

    Output

    0~180Vrms,12Arms,18A(peak value)

    CT Ratio

    Range

    1~40000

    accuracy

    ±0.05%

    PT Ratio

    Range

    1~40000

    accuracy

    ±0.2%

    Phase

    Range

    ±5min

    accuracy

    0.5min

    DC resistance

    Range

    0~300Ω

    accuracy

    2%±2mΩ

    Burden

    Range

    0~300VA

    accuracy

    2%±0.2VA

    Power supply

    AC220V±10%,50/60Hz

    Environmental Conditions

     Operating temperature :-10οC ~50οC,Humidity :≤90%

    Weight and Dimensions

    Dimensions:340 mm×300 mm×150mm,Weight<9kg


    CT PT Analyzer (3)CT PT Analyzer (4)

    User Interface And Method Of Operation

    2.1 Current transformer 
    In Para interface,use the Rotating mouse to switch cursor in transformer type frame,then choose the current transformer (CT).
    2.1.1 Test connection
    Used for selecting one or more experiment item, including four options such as resistance, excitation, ratio, burden etc. According to transformer type, four options can be combinated as shown in below table.
    Table 2.1   CT experiment project description

    experiment item

    Description

    Connection diagram

    resistance

    excitation

    ratio

    burden

    Measure CT’s secondary winding resistance Fig 2.1,can disconnection if measuring primary winding.
    Measure CT’s secondary winding resistance and excitation characteristic Fig 2.1,can disconnection if measuring primary winding.
    Measure CT’s secondary winding resistance, check it’s ratio and polarity Fig 2.1
    Measure CT’s secondary winding resistance and excitation characteristic, check it’s ratio and polarity Fig 2.1
    Measure CT’s secondary burden Fig 2.2
    Note:the ‘√’ means valid ,and the blank means invalid
    Step:
    Step 1. According to the CT testing project description of the table 2.1 to wiring(For all the CT structures,please refer to the description of appendix D for the actual connection mode)
    Step 2. The other windings of the same CT should be opened,CT’s primary side to grounding, equipment should be also to ground
    Step 3. Power on and prepare parameters Settings.
    Step 4. Then switch cursor to the “start” button to start
    Whether you are a power utility, maintenance provider, or transformer manufacturer, our Transformer Analyzer is the ideal tool for ensuring the optimal performance and reliability of your transformers. It is a valuable asset for preventive maintenance, condition assessment, and quality control, ultimately contributing to the efficiency and longevity of your power infrastructure.
    In conclusion, our Transformer Analyzer is a versatile and reliable solution for all your transformer testing and analysis needs. With its advanced features, user-friendly interface, and robust construction, it is the perfect choice for professionals seeking accurate, efficient, and comprehensive transformer testing.