Huazheng HZJB-1200 OEM Portable secondary Current Injection tester 6 Phase Relay Protection Tester
Device Features And Technical Parameters
Operation mode
The device is directly connected with a computer or a desktop computer, which is convenient and efficient and stable performance.
A new hi-fi linear power amplifier
The output port has always insisted on using the modular linear power amplifier instead of the switching power amplifier, which has the high fidelity and high reliability function and excellent performance. High-mid frequency will not be produced to disturb the test, also ensure the smoothing accuracy of waveform produced by the whole course of the high current to the tiny current is excellent.
High performance Mainframe
The output part adopts DSP control, which has fast operation, real-time digital signal processing capability, wide bandwidth and high resolution D/A conversion control. The output waveform has the features of high precision, small distortion and good linearity. With using a large number of advanced technology and precision components and materials and the structure of professional design, the device has the features of small volume, light weight, full function, easy to carry, boot can work, flow test is very convenient.
Powerful software function
It can complete all kinds of high automatic validation work which is large and complex. It can also conveniently test and scan protection setting, playback of fault, real-time store test data, display vector, online print report and so on. Besides, six-phase current can facilitate the test of three-phase differential protection.
Independent DC power output
An 110V and 220V adjustable DC power is designed to supply output.
Complete interface
The device with USB communication port can communicate with the computer and other external devices.
Perfect self-protection function
With reasonable design of the heat dissipation structure and the reliable and perfect hardware protection measures, it has the power soft start function and the software of the fault self-diagnosis and the output latch function.
Section 2 Nominal Parameter
Parameter
Type |
|
Current channel number |
Standard six phase |
Voltage channel number |
Standard six phase |
AC current output range |
30A / phase or 180A (six phase parallel) |
DC current output range |
10A DC /phase |
AC voltage output range |
120V AC /phase |
DC voltage output range |
160V DC / phase |
Nominal parameter
AC current output
The real value of each phase output when six phase current output 0~30A output precision 0.2 grade
The real value of each phase output when three phase current output 0~60A
The real value of six phase parallel current output 0~180A
The allowed real value when the phase current work long time 10A
The maximum output power of phase current 450VA
The maximum output power when six phase parallel current output 1000VA
The allowed working time when six phase parallel current maximum output 10s
Frequency range(fundamental wave) 0~1000Hz
Harmonic order 0~20
DC current output
Current output 0~±10A / phase output precision 0.2 grade
The maximum load volatage output 20V
AC voltage output
The real value of phase voltage output 0~120V output precision 0.2grade
The real value of line voltage output 0~240V
The output power of phase voltage/ line voltage 80VA / 100VA
Frequency range(fundamental wave) 0~1000Hz
Harmonic order 0~20
DC voltage output
The output amplitude of phase voltage 0~±160V output precision 0.2 grade
The output amplitude of line voltage 0~±320V
The output power of phase voltage/ line voltage 70VA / 140VA
Input and output
8 channels input
Free contact 1~20mA,24V
Electric potential contacts “0”:0 ~ +6V; “1”:+11 V ~ +250 V
4 channels output DC:220 V/0.2 A;AC:220 V/0.5 A
Time measurment range
0.1ms ~ 9999s , measurement accuracy <0.1ms
RELAY PROTECTION TEST ITEM INDEX
The index is designed to guide the tester that all kinds of the relay protection device test can be done by the following series which modules of software.
Relay test:
Relay protection type |
Test Item |
Proposed test module |
Remarks |
Signal relay |
Corresponding test items |
DC Test
AC and DC Test |
If the intermediate relay is required AC/DC hybrid input, please test in ‘The AC And DC Test ‘module. If Rated current of the signal relay is too small, please use the voltage loop output of tester to do experiments. |
Time relay |
|
|
|
Intermediate relay |
|
|
|
Coincidence relay |
|
|
|
Other DC voltage and current relay |
|
|
|
Current relay |
Corresponding test items |
AC Test |
The sequence component relay can be tested in the special sequence module of ‘AC Test’. The inverse time relay can be tested in the "It characteristics" module. |
Over (under) voltage relay |
|
|
|
Sequence component relay |
|
|
|
Synchronous check (or phase comparison) relay |
|
|
|
Inverse time current relay |
|
|
|
Differential relay |
DC magnetic feature |
Differential Relay, Differential Harmonic, AC/DC Test, Harmonic Test |
Please refer to ‘Appendix 5’ for correct wiring in the test |
|
Harmonic braking feature |
|
|
|
Proportional braking feature
|
Differential Relay, AC Test |
|
Power (directional) relay |
Corresponding test items |
Power Direction &Impedance, AC Test |
Before testing the power (direction) relay, the type of connection and the action boundary of the protection should be determined in advance. |
Impedance relay |
|
|
|
Synchronous relay |
Corresponding test items |
Synchronization Test, AC Test |
UA, UC of tester is fixed as the system side and the side to side voltage output for ‘Synchronization Test’ module. |
Frequency relay |
Corresponding test items |
High-Low Frequency Test |
When the ‘automatic frequency conversion’ method is chosen in the single machine, the frequency slip value can be measured. |
Computer protection test:
|
Relay protection type |
Test Item |
Proposed test module |
Remarks |
Line protection |
Multi-section over current |
Corresponding test items |
AC Test |
As long as the method is proper, the tests of most relays and microcomputer protection can be done by the ‘AC Test’ module, which should be selective learning. |
|
Over (under) voltage |
|
|
|
|
Sequence component voltage and current |
|
|
|
|
Frequency device |
|
|
|
|
Power direction protection |
|
|
|
|
Reclosing and tansform fault |
Corresponding test items |
Full Group Test, State Series, Comprehensive Test of Line Protection of 6-35 KV Microcomputer |
Requirement that if the Synchronization check and no-voltage check test is done, the Ux as the side and side voltage output and the tester is to use Ua instead of Ux for testing. |
|
Distance & Zero Sequence Protection, |
The Setting value verification of Distance & Zero Sequence Protection |
Distance & Zero Sequence Protection, Full Group Test, AC Test |
"Distance & Zero Sequence Protection” can automatically test multiple sections, various fault types and other distance and zero sequence value. |
|
|
Characteristic of Impedance |
Characteristic of Impedance |
|
|
Power frequency variation distance |
Setting value verification |
Distance & Zero Sequence Protection |
The fault current should be large enough, such as 10~15A (when CT is 5A) |
|
Compound voltage blocking(directional) overcurrent |
Over current, low voltage, negative sequence voltage, sensitive angle |
AC Test, Comprehensive Test of Line Protection of 6-35 KV Microcomputer |
Some of the protection of the "low voltage" and "negative sequence voltage" input by different terminal, replacing the wiring is necessary in the test. |
|
Low cycle, low voltage load shedding device |
Corresponding test items |
High-Low Frequency Test, Comprehensive Test of Line Protection of 6-35 KV Microcomputer |
If other conditions are satisfied, the device cannot move, please confirm whether the device also need to input current and switch contacts |
The generator transformer protection |
Differential protection |
Proportional braking characteristic |
Differential Protection, Differential Value, AC Test |
When the differential protection is used in the differential protection of generator, it can be regarded as the transformer protection with the connection type of Y/Y, high and low voltage side balance coefficient of 1. "Differential protection" module pay attention to the curve characteristic search and the "differential value" module focuses on the differential value test. Their combination can test the differential protection. |
|
|
Harmonic braking characteristic |
Differential Protection, Differential Value, Harmonic Test |
|
|
Loss of magnetic protection |
Corresponding test items |
AC Test |
The angle of output voltage and current should be paid attention in the test. |
|
Excitation protection |
|
|
|
Other protection |
Automatic quasi synchronization device |
Corresponding test items |
Synchronization Test |
To do the automatic adjustment test, the line must be in accordance with the requirements of instruction when testing the input. |
|
Busbar differential protection |
Corresponding test items |
AC Test |
Please see the instructions of the BP-2B and RCS-915 of "Nari part protection" on in the Appendix 6. |
|
Optical fiber line differential protection |
|
|
Before the test to determine whether the device to form a "self loop", if, then the protection of the action value should be equal to half of its set value. |