Huazheng HZ-KG7 Vacuum Switch Tube Vacuum Degree Tester vacuum interrupter tester
Introduction
In JB8738-1998《vacuum interrupter arc chamber of 3.6-40.5KV AC high voltage switchgear》established by high-voltage switchgear National Standardization Technical Committee, it is prescribed that the internal gas pressure measurement and allowable storage time limit inspection must be executed for any user and producer of interruption arc chamber of high-voltage vacuum switchgear. At the same time, in National Standardization -JB8738-1998, it is also noticed that allowable storage time limit of interruption arc chamber should be 20 years, and internal gas pressure of the vacuum interrupter arc chamber should be less than 6.6×10-2Pa.
Inspection methods of Allowable Storage Time of Vacuum Interrupter Arc Chamber: measuring internal gas pressure of vacuum interrupter arc chamber should be with a pulsed magnetic vacuum meter, recode the pressure value P1 (Pa); after put the vacuum meter aside for period of time-t(d), measure the internal gas pressure of vacuum interrupter arc chamber with this vacuum meter again, and recode the pressure value P2 (Pa), holding time t should be less than 7d. By the following formula, the allowable storage time of vacuum interrupter arc chamber can be calculated:
HZ-KG7 Vacuum Switch Vacuum Tester for vacuum switchgear is the latest generation of products of my company, it is the upgrade product in the base of HZ-KG6 vacuum meter on the foundation of notion from the field user. HZ-KG7 Vacuum Switch Vacuum Tester has some features- higher measurement accuracy, better stability, more capacity.
For vacuum circuit breaker, the method of determining whether or not deterioration of the vacuum tube is inspection with the method of frequency withstand voltage, but this method only distinguish the vacuum interrupter arc chamber of the serious deterioration. When the vacuum of vacuum interrupter arc chamber degrade to 10-2-10-1 Pa, although the breakdown voltage is not reduced, but the interrupter arc chamber has failed. In the HZ-KG7 Vacuum Switch Vacuum Tester for vacuum switch, the new field coils were used, and with the magnetron discharge method the vacuum of the vacuum interrupter arc can be measured without disassembling the interrupter arc chamber.
Specifications
Packing list
No. |
Item |
Qty |
1 |
Magnetic coil |
1 |
2 |
High voltage output line |
1 |
3 |
Lonic current line |
1 |
4 |
Magnetic field voltage line |
1 |
5 |
Ground line |
1 |
6 |
Elastic straps |
1 |
7 |
Coil sling |
1 |
8 |
Meter stick |
1 |
9 |
Printing paper |
2 |
10 |
Power cable |
1 |